MR-US40KTS-HP33-TLE

Protect Your Data and Devices

Output: 40kVA / 40kW


  • High Frequency Online UPS 3P3P

    40kVA / 40kW
  • •  DSP technology guarantees high performance
    • Output power factor 1.0
    • Emergency power off function (EPO)
    • ECO mode operation for energy saving (ECO)
    • Active power factor correction in all phases
    • 3-stage extendable charging design for optimized battery performance
    • SNMP+USB+RS-232 multiple communications
    • Generator compatible
    • Optional isolation transformer offers full isolation and complete common mode noise rejection
    • Maintenance bypass available
    • Adjustable battery numbers for long-run model

Leave a message

隐藏域元素占位

  • Overview
  • Specifications
  • Downloads
  • Support
  • 概要
  • High Frequency Online UPS 3P3P

    40kVA / 40kW

Expand All

High Frequency Online UPS 3P/3P (S)
Model MR-US10KTS-HP33-TLE MR-US20KTS-HP33-TLE MR-US30KTS-HP33-TLE MR-US40KTS-HP33-TLE
Phase 3Ph in 3Ph out (3P1N)
Rated Capacity 10kVA / 10kW 20kVA / 20kW 30kVA / 30kW 40kVA / 40kW
Parallel Capability up to 4 units in parallel
Output
Output Voltage 3 x 360*/380*/400/415 VAC (3Ph+N)
AC Voltage Regulation (Batt. Mode)

± 1 %

Frequency Range (Synchronized Range) 46 – 54Hz @ 50Hz system; 56 – 64Hz @ 60Hz system
Frequency Range (Batt. Mode) 50Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Waveform (Batt. Mode) Pure Sine wave
Current Crest Ratio 3:1 (max.) 
Transfer Time AC Mode to Batt. Mode 0ms
Inverter to Bypass 0ms
Harmonic Distortion (THDi) ≤2% THD (Linear Load) ; ≤5 % THD (Non-linear Load) 
Overload Capability 100 – 110% for 60min, 111 – 125% for 10min, 126% – 150% 1min, >150% immediately
Input
Nominal Voltage 3 x 400VAC (3Ph+N) / 230VAC (1Ph+N)
Voltage Range (Ph-N) 110 – 300VAC ± 3 % @ 50% load; 176 – 276VAC ± 3 % @ 100% load
Frequency Range 46 – 54Hz @ 50Hz system; 56 – 64Hz @ 60Hz system
Power Factor ≥0.99 @ 100% Load
Harmonic Distortion (THDi) <4% at full linear load
BYPASS (S)
Bypass
Nominal Voltage 3 x 380 / 400 / 415VAC (3Ph+N)
Voltage Range (Ph-N) -30% – +20% (Adjustable)
Frequency Range (Synchronized Range) 46 – 54Hz or 56 – 64Hz
Overload Capability >130% 1 minute (default) ; continuously working until breaker protection (optional)
Efficiency
AC Mode 95.50%
ECO Mode 98.50%
Battery Mode 94.50%
Battery
Battery Spec 12V / 9Ah 12V / 9Ah 12V / 7Ah 12V / 9Ah
Numbers (10+10) pcs (16+16) pcs 2*(16+16) pcs 2*(16+16) pcs
Charging Current (max.) 1A (Default) 2A (Default)
Charging Voltage +/-136.5 VDC ± 1% +/-218 VDC ± 1% +/- 13.65 V*N ± 1% (N = 16~20)
Indicators
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Physical
Net Weight (kg) 124 139 207 233
Dimension, D*W*H (mm) 630 x 250 x 826 815 x 300 x 1000
Environment
Operation Temperature 0 – 40°C
Operation Humidity <95% and non-condensing
Altitude** 0 – 1500m at full load
Noise Level Less than 60dB @1 Meter Less than 65dB @1 Meter   Less than 70dB @1 Meter
Management
Smart RS-232 / USB

Supports Windows® Family, Linux and MAC

Optional SNMP Power management from SNMP manager and web browser

 

  *If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.
  *If output voltage is set as 3 x 360VAC or 3 x 380VAC, the output power of the unit will be de-rated to 90%.

 

 

Support

Please contact our Tech Support department with installation, troubleshooting, or general product questions.

Hours of operation: Monday – Friday 9 : 00am – 9 : 00pm UTC+8

Our Technical Support team will be happy help you with technical questions during business hours. 

Contact Tech Support: Submit Ticket Now


Submit a Support Ticket

Global

English

Submit a message