MR-UT3000
Steady Voltage, Steady Performance
Output: 3000VA / 3000W
-
SOHO Inverter
MR-UT3000
3000VA / 3000W
-
● Pure sine wave output.
● Microprocessor based design.
● Smart charging.
● Speed control for cooling fan.
● Real time auto-detection for battery condition.
● Protection for overload, short circuit, & over temp.
● Isolation between battery and AC utility.
● Outstanding dynamic performance.
隐藏域元素占位
- Overview
- Specifications
- Downloads
- Support
- 概要
-
SOHO Inverter
MR-UT3000
3000VA / 3000W
Expand All
Model | MR-UT2000 | MR-UT3000 | |||||
Input Voltage Waveform | Sinusoidal (Utility or generator) | ||||||
Nominal lnput Voltage | 230VAC | ||||||
Low Line Disconnect | UPS mode: 180VAC±4% INV mode:160VAC±4% | ||||||
Low Line Re-connect | UPS mode: 190VAC±4% INV mode:170VAC±4% | ||||||
High Line Disconnect | UPS mode: 265VAC±4% INV mode:265VAC±4% | ||||||
High Line Re-connect | UPS mode: 255VAC±4% INV mode:255VAC±4% | ||||||
Nominal lnput Frequency | 50Hz / 60Hz (Auto detection) | ||||||
Low Line Frequency Re-connect | 58±0.3Hz for 60Hz; 45±0.3Hz for 50Hz; | ||||||
Low Line Frequency Disconnect | 57±0.3Hz for 60Hz; 45±0.3Hz for 50Hz; | ||||||
High Line Frequency Re-connect | 64±0.3Hz for 60Hz; 54±0.3Hz for 50Hz; | ||||||
High Line Frequency Disconnect | 65±0.3Hz for 60Hz; 55±0.3Hz for 50Hz; | ||||||
Output Voltage Waveform | As same as input wave form | ||||||
Over Load Protection (SMPS load) | Circuit breaker | ||||||
Output Short Circuit Protection | Circuit breaker | ||||||
Efficiency(Line Mode) | >95% | ||||||
Transfer Time(AC to DC) | ≤10ms (Typical) | ||||||
Transfer Time(DC to AC) | ≤10ms (Typical) |
Model |
HV MODEL |
||||||
MR-UT2000 | MR-UT3000 | ||||||
Output Voltage Waveform | Sine wave | ||||||
Rated Output Power (VA) | 2000 | 3000 | |||||
Rated Output Power (W) | 2000 | 3000 | |||||
Power Factor | 0 - 1.0 | ||||||
Nominal Output Voltage (V) | 230VAC | ||||||
Nominal Output Frequency (Hz) | 50Hz ± 0.3Hz | ||||||
Auto tracking Main Frequency (Hz) | Yes (Following main first connection) 50Hz@45-54Hz / 60Hz@55-64Hz | ||||||
Output Voltage Regulation | ±10%rms | ||||||
Nominal Efficiency | >80% | ||||||
Over Load Protection (SMPS load) | (100%<load<120%)± 10% : Fault (Shutdown output) after 2 minutes; (120%<load<140%)±10% : Fault (Shutdown output) after 1 minutes, Load>140%±10% : Fault (Shutdown output) after 20s |
||||||
Surge rating (10s) | 6000VA | 9000VA | |||||
Capable of starting electric motor | 1 HP | 2HP | |||||
Output Short Circuit Protection | Current limit (Fault after 10s) | ||||||
Nominal DC lnput Voltage | 24V | ||||||
Min DC Start Voltage | 20V | ||||||
Low Battery Alarm | 21.0VDC ± 0.6VDC for 24V battery | ||||||
Low DC lnput Shut-down | 20.0VDC ± 0.6VDC for 24V battery | ||||||
High DC lnput Alarm & Fault | 32VDC ± 0.6VDC for 24V battery | ||||||
High DC lnput Recovery | 31.0VDC ± 0.6VDC for 24V battery | ||||||
Power saver | Load≤25W (Enabled on“P/S auto”setting of Remote control) |
Model |
HV MODEL |
||||||
MR-UT2000 | MR-UT3000 | ||||||
Nominal Input Voltage | 230VAC | ||||||
Input Voltage Range | UPS mode: 180 – 265VAC ± 4% INV mode: 160 – 265VAC ± 4% |
||||||
Output Voltage Range | UPS mode: 180 – 265VAC ± 4% INV mode: 160 – 265VAC ± 4% |
||||||
Nominal Charge Current | 45A (Max.) | ||||||
Charge Current Regulation | ±5ADC | ||||||
Charger Short Circuit Protection | Circuit Breaker | ||||||
Over Charge Protection | Bat.V≥ 31.4VDC, beeps 0.5s every 1s & fault after 60s | ||||||
Charge Algorithm | Three stage: Boost CC (Constant current stage) —— Boost CV (Constant voltage stage) —— Float (Constant voltage stage) | ||||||
Charge Stage Transition Definitions | Boost CC Stage: If A/C input is applied, the charger will run at full currentin CC mode until the charger reaches the boost voltage. | ||||||
Boost CV Stage: In this stage,the charger will keep the boost voltage in Boost CV mode.The charging current will reduce, until less than 2A, then drop the voltage down to the float voltage. | |||||||
Float Stage: In float mode,the voltage will stay at the float voltage. If the A/C is reconnected or the battery voltage drops below 12VDC / 24VDC / 48VDC, the charger wil reset the cycle above. |
Specifications are subject to change without notice, and all product drawings are for reference only. Consult MARSRIVA for the latest design and specifications.
Downloads
Support
Please contact our Tech Support department with installation, troubleshooting, or general product questions.
Hours of operation: Monday – Friday 9 : 00am – 9 : 00pm UTC+8
Our Technical Support team will be happy help you with technical questions during business hours.
Contact Tech Support: Submit Ticket Now
Submit a Support Ticket